Beckett Boiler: NX burner: setting combustion with an analyzer

Updated · by Aurora Star Tech Inc.

NX burner: setting combustion with an analyzer on a Beckett boiler: Start-up air settings from Table 1 are only a starting point. Final air must be set with smoke and CO2/O2 readings.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)

Common causes of nx burner: setting combustion with an analyzer

  • New install or nozzle change
  • Smoke, soot or poor efficiency

How to fix nx burner: setting combustion with an analyzer: step by step

  1. Drill a 1/4 in. test hole in the flue pipe between the boiler and the barometric damper. Seal it when done.
  2. Check zero calibration of the head/air plate, then set the pointer: go half a number below the target and come back up to it.
  3. Run the burner 5 to 10 minutes.
  4. Turn the head/air screw until you see a trace of smoke (counter-clockwise = more air, clockwise = less).
  5. Read CO2 (or O2) at that trace-of-smoke point. Example in the manual: 13.5% CO2 / 2.6% O2.
  6. Add air until CO2 drops 1.5 to 2 points (O2 goes up about 2.0 to 2.7 points). Example: 13.5% down to 11.5% CO2. Smoke must read zero.
  7. Set draft to the boiler maker's number. Natural draft is usually -0.01 to -0.02 in. w.c. over-fire. Direct vent usually needs no draft setting.
  8. Chimney vent: put the cover on and recheck. If CO2 rises with the cover on, take it off and add air until the reading with the cover on is right.
  9. Tighten the lower acorn nut and splined nut. Start and stop the burner several times and test the primary and all boiler safety controls.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Beckett Boiler codes

Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Start-up and initial settings p.14-15; Set combustion with test instruments p.15-16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.