Beckett Boiler: NX burner: Honeywell R7184 primary sequence and lockout
NX burner: Honeywell R7184 primary sequence and lockout on a Beckett boiler: Some NX burners use a Honeywell R7184 primary instead of the GeniSys 7505. Its timing is different.
Applies to: Beckett NX burners with Honeywell R7184 primary on Weil-McLain Ultra Oil boilers
Common causes of nx burner: honeywell r7184 primary sequence and lockout
- No flame within the 15 s trial for ignition
- Flame lost three times in a row
How to fix nx burner: honeywell r7184 primary sequence and lockout: step by step
- Before any reset: look in the chamber. If oil has pooled or the boiler is full of oil vapor, shut off power and oil, let it cool and clean it out first. Never try to relight a hot, vapor-filled chamber.
- On a call for heat the control does a 3 to 10 second safe-start check. If the burner does not start after that, the control may need its safety reset.
- Valve-on delay: igniter and motor run 15 s before the oil valve opens.
- Trial for ignition: flame must be proven within 15 s or the control locks out and must be reset by hand.
- Three lockouts in a row put it into restricted lockout.
- Once lit, the igniter stays on 10 s (or the whole run if wired for intermittent ignition).
- Flame lost while running: 60 s recycle delay, then it tries again. Three flame losses in a row = lockout.
- Feature list: R7184P has the diagnostic LED, cad cell indicator, valve-on delay and motor-off delay; R7184A/B have fewer features.
If the unit shows an error code, look it up: Beckett Boiler codes
Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Figure 9 R7184P sequence of operation and control features p.14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.