Beckett Boiler: AFG burner: setting combustion with an analyzer

Updated · by Aurora Star Tech Inc.

AFG burner: setting combustion with an analyzer on a Beckett boiler: How to set the air on an AFG burner so it has reserve air and zero smoke.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Beckett AF/AFG oil burners (0.40-3.00 GPH) on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers

Common causes of afg burner: setting combustion with an analyzer

  • Air setting not done with instruments
  • Draft changed since last set-up
  • Cover installed after setting (changes the air)

How to fix afg burner: setting combustion with an analyzer: step by step

  1. Run the burner 5 to 10 minutes first.
  2. Set over-fire draft to the boiler maker's number. Natural draft is usually -0.01 to -0.02 in. w.c. Direct vent usually needs no draft adjustment.
  3. Close the air down until you get a trace of smoke. Measure CO2 (or O2) there. This is your reference, for example 13.5% CO2 / 2.6% O2.
  4. Open the air to drop CO2 by 1.5 to 2 points (O2 goes up about 2.0 to 2.7 points). Example: 13.5% down to 11.5% CO2.
  5. Check smoke again. It must be zero.
  6. Tighten the air band, shutter and head plate.
  7. If the burner has a cover, put it on and re-test. If CO2 goes up with the cover on, take it off and open the air a bit more.
  8. Start and stop the burner several times and test the primary control and boiler safeties.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Beckett Boiler codes

Source: Beckett AF/AFG Burner Manual for Weil-McLain WGO/WTGO/SGO boilers (550-143-079/1224), Set combustion with instruments, p.15-16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.