Beckett Boiler: AFG burner on biodiesel: analyzer reads CO2 low

Updated · by Aurora Star Tech Inc.

AFG burner on biodiesel: analyzer reads CO2 low on a Beckett boiler: Most analyzers have no biodiesel fuel setting, so CO2 is calculated wrong on bio blends.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Beckett AF/AFG oil burners (0.40-3.00 GPH) on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers

Common causes of afg burner on biodiesel: analyzer reads co2 low

  • Analyzer set to #2 oil while burning a biodiesel blend

How to fix afg burner on biodiesel: analyzer reads co2 low: step by step

  1. Set the analyzer fuel type to light oil / #2 oil.
  2. On B100 the analyzer shows CO2 about 0.3% lower than it really is. Add 0.3% to the reading. On B20 the error is under 0.1%.
  3. Better: set up by O2, which is measured directly. For bio blends aim for 4.5 to 5.7% O2 (about 11.3 to 12.3% CO2).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Beckett Boiler codes

Source: Beckett AF/AFG Burner Manual for Weil-McLain WGO/WTGO/SGO boilers (550-143-079/1224), Analyzers with biodiesel blends, p.16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.