Beckett Boiler: AFG burner at low firing rate: low firing rate baffle

Updated · by Aurora Star Tech Inc.

AFG burner at low firing rate: low firing rate baffle on a Beckett boiler: At firing rates under about 1.00 GPH the AFG may need the low firing rate baffle (LFRB) to cut air flow and pressure. Weil-McLain calls for it on the WGO-2, WGO-3R and WGO-4R and on the Ultra Oil UO-3 at 0.80 GPH.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Beckett AF/AFG oil burners (0.40-3.00 GPH) on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers

Common causes of afg burner at low firing rate: low firing rate baffle

  • Low firing rate baffle missing where the boiler table calls for it
  • Air setting too high for a small nozzle

How to fix afg burner at low firing rate: low firing rate baffle: step by step

  1. Power off before opening the burner.
  2. Check the boiler maker's burner table for the model. If it calls for the LFRB, make sure it is installed. Do not leave it out.
  3. Max rate with the LFRB by head: F0 up to 0.65 GPH; F3, L1, L2 up to 0.85; F4, F6 up to 0.90; V1 up to 1.00 GPH.
  4. Re-check the Z dimension if the air tube or nozzle line was changed.
  5. Set combustion with an analyzer after the change.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Beckett Boiler codes

Source: Beckett AF/AFG Burner Manual for Weil-McLain WGO/WTGO/SGO boilers (550-143-079/1224), Low firing rate baffle and Figure 9, p.9; burner spec table p.4-5; Beckett AFG Burner Manual for Weil-McLain Ultra Oil boilers (0225) spec table. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.