Lennox Heat Pump Outdoor unit clearances

Updated · by Aurora Star Tech Inc.

Lennox Heat Pump Outdoor unit clearances: reference table for the heat pump (Lennox ML14KP1 series): a quick-reference table with notes.

Heat PumpClearancesLennox ML14KP1

Lennox Heat Pump Outdoor unit clearances table

LocationClearance
Service side (one side next to control box)24 in. (610 mm)
One of the other three sides36 in. (914 mm)
One of the remaining two sides12 in. (305 mm)
Last side6 in. (152 mm)
Top48 in. (1219 mm)
Multi-unit, between units12 in. (305 mm) minimum [18 in. (457 mm) recommended] or 24 in. (610 mm) depending on layout
Multi-unit service side24 in. (610 mm) recommended
Above roof surface (roof mount)6 in. (152 mm) minimum

How to use the Lennox Heat Pump Outdoor unit clearances table

Find your exact model in the first column and read across the row. Values in the Lennox Heat Pump Outdoor unit clearances table are a summary for quick reference; the rating plate on the unit and the manufacturer's manual for your model always decide. If your model is not listed, or a value looks different from what you see on the unit, check the manual before changing anything.

Notes

  • Multi-unit spacing (A/B) depends on single row, wall or multiple rows layout - see figure on p.7.
  • Increase clearances where snow/ice can fall on the unit or air can recirculate.

Applies to: Lennox ML14KP1 heat pumps

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Lennox models this applies to

ML14KP1-018ML14KP1-024ML14KP1-030ML14KP1-036ML14KP1-042ML14KP1-048ML14KP1-060

Lennox Heat Pump error codes →

Source: Lennox ML14KP1 Unit Information 100108 (03-2026), Installation Clearances p.7, Roof Mounting p.14. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.