ICP Heat Pump Outdoor unit clearances
ICP Heat Pump Outdoor unit clearances: reference table for the heat pump (ICP N4H3 Heat Pump series): a quick-reference table with notes.
ICP Heat Pump Outdoor unit clearances table
| Location | Minimum |
|---|---|
| Above unit (discharge) | 48 in. (1.2 m) |
| Each coil side (intake) | 18 in. (457 mm) |
| One coil side, reduced (unit to structure) | 6 in. (152 mm) |
| Control box corner and service panel | 24 in. (610 mm) |
| Between side-by-side units | 18 in. (457 mm) |
| Roof overhang above unit (with gutters) | 48 in. (1.2 m) vertical |
How to use the ICP Heat Pump Outdoor unit clearances table
Find your exact model in the first column and read across the row. Values in the ICP Heat Pump Outdoor unit clearances table are a summary for quick reference; the rating plate on the unit and the manufacturer's manual for your model always decide. If your model is not listed, or a value looks different from what you see on the unit, check the manual before changing anything.
Notes
- Small objects (post, fence end): clearance about equal to the object width.
- Do not install under an overhang without gutters.
Applies to: ICP N4H3 R-410A split-system heat pumps (all sizes)
ICP models this applies to
Source: ICP N4H3 Installation Instructions 428 01 5103 02, Clearances, PDF p.3 (printed p.2). Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.