Updated · by Aurora Star Tech Inc.

No heat - Daikin DR96TN/DD96TN on a Daikin furnace: Thermostat calls for heat but the furnace does not start, light or deliver heat. Step-by-step check of the heating sequence from the manufacturer flowchart.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Common causes of no heat - daikin dr96tn/dd96tn

  • No power or blown board fuse
  • Open thermostat circuit
  • Inducer or pressure switch problem (vent, drain, hose)
  • Igniter or control board output failure
  • No gas, low gas pressure or failed gas valve
  • Dirty flame sensor or poor ground
  • Blower motor or harness failure
  • Furnace in R-32 mitigation mode (EAF/EAL/EAS/EAr shown)

How to fix no heat - daikin dr96tn/dd96tn: step by step

  1. If the display shows EAF, EAL, EAS or EAr the furnace is in R-32 mitigation mode (fan only, no gas heat) - fix that code first.
  2. Check the furnace power switch and breaker are on and the thermostat is set to heat above room temperature.
  3. Measure 115 VAC between line H and N on the control board. None: check the breaker, service switch and blower door switch.
  4. Check 115 VAC at the transformer primary and 24 VAC at the secondary. Primary OK but no secondary: check for a short, then replace the transformer.
  5. 24 VAC at the transformer but not between R and C on the board: replace the board fuse (find the short first).
  6. No 24 VAC between W (W1) and C with a heat call: the thermostat or its wiring is open.
  7. Inducer not running: check 115 VAC at the inducer. No voltage = control board or inducer wiring; voltage but no run = inducer bad or off on its thermal protector (check for over-voltage).
  8. Pressure switch not closing: measure the negative pressure at the switch. Enough vacuum = replace the switch; not enough = check venting, drainage, water in the inducer and a plugged switch port.
  9. No 115 VAC to the igniter after pre-purge: replace the control board. Voltage but no glow: replace the igniter. Igniter glows only part of the warm-up: check for the pressure switch opening during warm-up.
  10. Gas valve must open and hold proper manifold pressure for at least 4 seconds. If not: confirm house gas pressure, 24 VAC at the valve wires, and 24 VAC between HI/M and common; on 90% models check the front cover pressure switch in series with the valve, on 80% models check for an open auxiliary limit in series with the valve; then replace the valve.
  11. Burners do not light or will not stay on: check burner dirt and alignment, orifice plate position, flooded or blocked heat exchanger, flame signal, ground wires, and that all pressure switches stay closed.
  12. Blower does not start about 30 seconds after ignition: check 115 VAC between CIRC-H and neutral and at the motor L/N, then the speed tap signal between motor common and a T terminal; check the harness, then the motor.
  13. Burners shut off before the thermostat is satisfied: read the fault code and compare the actual temperature rise with the rating plate.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Furnace codes

Models

DD96TN0403BNDD96TN0603BNDD96TN0803BNDD96TN1005CNDR96TN0303ANDR96TN0403ANDR96TN0603ANDR96TN0603BNDR96TN0803BNDR96TN0804CNDR96TN1004CNDR96TN1005CNDR96TN1205DN

Source: Daikin RSD6612304, 90% Heating (2 Stage) No Heat flowchart, p.33-34. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.