Carrier Air Conditioner: Amber STATUS or green COMM light not on
Amber STATUS or green COMM light not on on a Carrier air conditioner: Two little lights on the outdoor board of your Carrier Infinity 19VS (24VNA9) can tell you a lot. The amber STATUS light and the green COMM light on the AOC board show whether the board has power and whether it is talking to the indoor unit. If the amber light is off with power on, the board is most likely dead. The green light is a bit different, because with a non-communicating thermostat it is normally off, so check what you have before you start swapping parts. Wall control code 179 is a good hint too.
Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9
Common causes of amber status or green comm light not on
- AOC board failure
- No communication with the indoor unit or wall control
- Non-communicating thermostat, where the COMM light is normally off
- A and B communication wires open, loose or swapped
How to fix amber status or green comm light not on: step by step
- With power to the outdoor unit the amber STATUS light must be on or flashing, if it is completely off, confirm the unit has supply voltage and then replace the AOC board
- Communicating systems: the green COMM light should be on steady once the indoor unit and Infinity control talk to it, it goes off after 2 minutes without communication
- If A and B wires are connected and the indoor unit communicates but COMM stays off, replace the AOC board
- Check the A and B wires at both ends for tight connections
- Wall control code 179 means lost communication with the outdoor AOC, the AOC or inverter may need replacing
- Turn power off at the disconnect before working on the wiring
If the unit shows an error code, look it up: Carrier Air Conditioner codes
Models
Carrier 2-stage 24ANB/25HNB
24ANB12424ANB13624ANB14824ANB16024ANB72424ANB73624ANB74824ANB760
Carrier Infinity 19VS 24VNA9
24VNA924VNA91324VNA92424VNA92524VNA93624VNA93724VNA94824VNA94924VNA960
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Communication and Status Function Lights p.8; LED tables p.27-28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.