Mitsubishi Heat Pump: Indoor board LED2 blinking – remote controller line problem
Indoor board LED2 blinking - remote controller line problem on a Mitsubishi heat pump: LED2 on the indoor control board blinks. If LED1 blinks too, the indoor/outdoor wire is the problem; if LED1 is steady, look at the remote controller line.
Applies to: PEAD-RP35/50/60/71/100/125/140JA and JA(L) ducted indoor units (220-240 V models)
Common causes of indoor board led2 blinking - remote controller line problem
- Indoor/outdoor connecting wire loose (LED1 also blinking)
- On twin/triple systems, remote wired to more than one indoor unit
- Refrigerant address wrong, or more than one unit at address 0 in a group
- Remote controller wire shorted
- Faulty remote controller
How to fix indoor board led2 blinking - remote controller line problem: step by step
- If LED1 is also blinking, check the S1-S2-S3 connections.
- On twin/triple systems, connect the remote to only one of the indoor units.
- In group control, make sure only one system uses address 0 (SW1 3-6 on the outdoor board).
- Disconnect the remote wire: if LED2 keeps blinking, the remote wire is shorted. If LED2 goes steady, reconnect - blinking again means a bad remote; steady means the connection was the problem.
If the unit shows an error code, look it up: Mitsubishi Heat Pump codes
Models
PEAD-RP35JAPEAD-RP35JALPEAD-RP50JAPEAD-RP50JALPEAD-RP60JAPEAD-RP60JALPEAD-RP71JAPEAD-RP71JALPEAD-RP100JAPEAD-RP100JALPEAD-RP125JAPEAD-RP125JALPEAD-RP140JAPEAD-RP140JAL
Source: Mitsubishi Electric PEAD-RP35-140JA(L) Service Manual, 10-4 Troubleshooting by inferior phenomena, p.35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.