Mitsubishi Heat Pump: Indoor board LED1 and LED2 both off – no power
Indoor board LED1 and LED2 both off - no power on a Mitsubishi heat pump: Nothing on the indoor unit or remote works and both LEDs on the indoor control board are dark.
Applies to: PEAD-RP35/50/60/71/100/125/140JA and JA(L) ducted indoor units (220-240 V models)
Common causes of indoor board led1 and led2 both off - no power
- No power to the outdoor unit
- Faulty outdoor control board
- No power reaching the indoor unit on S1-S2
- Faulty indoor control board or blown fuse
How to fix indoor board led1 and led2 both off - no power: step by step
- WARNING: Line voltage present. Work only with proper PPE and meters rated for the circuit.
- Check voltage at the outdoor power terminal block. None = check the breaker and supply wiring.
- Check voltage between S1 and S2 at the outdoor terminal block. None = check the fuse on the outdoor board and its wiring.
- Check S1 to S2 at the indoor terminal block. None = check the indoor/outdoor wire for a wiring fault.
- If voltage is there, check the fuse on the indoor board and its connectors. If they are good, the indoor board is faulty.
If the unit shows an error code, look it up: Mitsubishi Heat Pump codes
Models
PEAD-RP35JAPEAD-RP35JALPEAD-RP50JAPEAD-RP50JALPEAD-RP60JAPEAD-RP60JALPEAD-RP71JAPEAD-RP71JALPEAD-RP100JAPEAD-RP100JALPEAD-RP125JAPEAD-RP125JALPEAD-RP140JAPEAD-RP140JAL
Source: Mitsubishi Electric PEAD-RP35-140JA(L) Service Manual, 10-4 Troubleshooting by inferior phenomena, p.35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.