Other: Boiler tips (part 47 of 50)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Propane operation requires the conversion kit
Weil-McLain · SlimFit 550/750 Series 3 boiler
SlimFit boilers ship set for natural gas only. Propane needs the conversion kit and orifice installed first, following the propane instructions in the front of the manual.
- Install the propane conversion kit before connecting propane.
- Install the propane orifice, which ships loose, when running on propane.
- Size the propane pipes, tanks and 100% lockup regulator with the gas supplier.
Propane-ready and factory propane models
Weil-McLain · Ultra-80, 105, 155, 230, 299, 399 and 80LP
Ultra boilers ship ready for natural gas only, unless the model is propane-ready. Propane-ready units have LP after the model number. Ultra-80LP is factory-equipped for propane.
- Check the model suffix before firing on propane.
- For non-LP models other than Ultra-399, install the propane orifice or conversion kit before propane firing.
- Ultra-80 natural gas units needing a burner conversion must use the special-order conversion kit instructions, not this manual.
Protect connections during storage and uncrating
Weil-McLain · SVF 500/600 boilers
Plastic components and connection covers must be protected until piping is attached.
- If the boiler was stored below 32°F (0°C), handle it carefully until the plastic parts reach room temperature.
- Leave plastic covers on the connections and adapters until piping is attached. This keeps debris out of the vent and air adapters.
Protect exposed vent pipe from freezing
Weil-McLain · Direct vent terminations
Do not extend exposed vent pipe outside the building beyond the length shown in the manual. Condensate can freeze and block the vent.
- Keep exposed vent pipe outside the building within the length shown in the manual.
- Check that condensate cannot freeze and block the vent pipe.
Protect low-temperature circuits on multi-temperature systems
Weil-McLain · Multi-temperature heating systems on Series 2 boilers
If the system has both low-temperature and high-temperature circuits, the low-temperature circuits need their own limit controls. Without them, property damage can occur.
- Wire limit controls on each low-temperature circuit to an external limit circuit.
- Confirm the limit controls regulate those circuits before commissioning.
Protect the boiler from low and cold return water
Weil-McLain · CGi-25 to CGi-8 low-temperature and radiant systems
Low return water temperature can corrode boiler sections and burners. Radiant and low-temperature systems need a way to control both return water temperature and supply temperature, for example with an injection pumping control. Do not use the bypass methods on systems with outdoor reset control. Those systems need controls and piping that hold the return water at no less than 130°F.
- Confirm the system supply temperature is fairly constant before using the bypass methods.
- If the system has outdoor reset control, provide controls and piping that hold return water at 130°F or higher.
- Contact the Weil-McLain representative for suggested piping and controls when outdoor reset is used.
Protecting and capping the concentric termination during install
Weil-McLain · 3 in or 4 in concentric termination assembly
Blocked air passages will stop the boiler from running, and cemented parts cannot be repaired. Keep debris out during installation, and do not alter the assembly.
- Wrap plastic or other protection over the end of the exposed assembly before inserting it through the roof or wall.
- Do not cement the rain cap until the assembly is through the penetration and all supports are installed.
- After positioning, place the bird screen on the end of the inner pipe, then cement the rain cap in place.
- Do not cut or alter the termination assembly. A cut part cannot be cleaned and must be replaced.
ProTools app: clone settings and update software over Bluetooth
Weil-McLain · ECO Tec Series 3 boilers with Unity 2.0 control
The ProTools app connects over Bluetooth. Its clone-to-phone feature copies settings from one boiler to another, and it can also update the boiler software.
- Connect the phone to the boiler over Bluetooth using the ProTools app.
- Use clone-to-phone to copy settings from one boiler to another.
- Update the boiler software through the app to get the latest features.
Purchased items needed for termination
Weil-McLain · Sidewall and vertical terminations
Bird screens, the concentric termination kit and the 45-degree elbow for concentric runs are not supplied with the boiler and must be bought separately.
- Check parts before starting. Concentric kit needs a separate 45-degree elbow in the piping.
- Maximum vent and air lengths already include the 45-degree elbow allowance.
Read and save boiler configuration with WM ProTools
Weil-McLain · ECO Tec Series 3 boilers with WM ProTools app
The app can load, save and view the boiler configuration. Saved files are stored on the phone only, so uninstalling the app deletes them. Save the information for your records.
- In the app, choose READ/WRITE Configuration.
- Press READ Configuration and wait several seconds for the data to load.
- Review the information, then press Save Configuration.
- Enter a descriptive name and press Save.
Read software versions
Weil-McLain · Unity control, SVF Series 1
The SOFTWARE VERSIONS screen shows the display version, main micro and second micro.
- Open DIAGNOSTICS > SOFTWARE VERSIONS.
- Record DISPLAY, MAIN MICRO and SECOND MICRO versions.
Read the last 3 lockout histories
Weil-McLain · SlimFit 1000-2000 Series 2
Shows the condition recorded at each of the last three lockouts.
- Scroll to DIAGNOSTICS and press Enter (square key in center).
- Scroll to ERRORS and press Enter.
- Scroll to LOCKOUT HISTORY # and press Enter.
- Choose MANUAL RESET or AUTO RESET and press Enter to see the fault recorded.
- Press the left arrow to return to LOCKOUT HISTORY #, scroll to another history, and press Enter for boiler details at the time.
Reading display colors and symbols
Weil-McLain · SlimFit Series 3 Control
Display color and symbols show the boiler state.
- Blue display: maintenance screen is active during standby, or space heating is active.
- Purple light: DHW is active.
- Red display: an error or limit event has occurred.
- Flashing red display: lockout condition.
- Wrench symbol in standby: maintenance is due.
Reinstall door and check gaskets after service
Weil-McLain · All Ultra Series 4 boilers
The boiler door must be sealed and fastened so the boiler does not draw air from the boiler room.
- Reinstall the boiler jacket front door after startup or service.
- Inspect the door gaskets; replace them if torn or gapped.
- Make sure the door is securely fastened.
Reinstall jacket door after servicing
Weil-McLain · ECO Tec Series 3 gas boilers
A properly sealed jacket door keeps the boiler from drawing air from the room.
- Reinstall the jacket door after start-up or service.
- Make sure it is securely fastened.
- Check the jacket door gaskets for tears or gaps and replace if needed.
Reinstall the front door after service
Weil-McLain · SlimFit 550 and 750 Series 3
Air can be drawn from inside the boiler room if the door is loose, which matters most when other appliances share the room.
- Reinstall the boiler jacket front door after servicing.
- Fasten the door securely to the boiler.
Reinstall the jacket door after service
Weil-McLain · All ECO Tec Series 3 models
The jacket door must be fastened securely after start-up or any service so the boiler does not pull air from the boiler room. This matters most when other appliances share the room. Check the door gasket on the cabinet front. It must have no tears or gaps and should be replaced if damaged.
- Reinstall the jacket door after start-up or servicing.
- Confirm the door is fastened securely.
- Inspect the door gasket for tears or gaps and replace it if needed.
Relief valve and by-pass regulator piping
Weil-McLain · Express Setup Examples C and D piping
The relief valve is supplied with the boiler and must be field piped to the boiler In connection. Relief valve piping runs to a drain. A by-pass pressure regulator is required in zone valve systems.
- Pipe the supplied relief valve to the boiler In connection; see Figure 12 on page 18.
- Run relief valve discharge piping to a drain.
- In zone valve systems, install a by-pass pressure regulator.
Relocate the control display to another burner-end panel
Weil-McLain · SlimFit Series 2 all models
The display can be moved from the factory front position to a burner-end panel. Do not move the display panel with its communication cable still connected.
- Remove the lower door panel under the display by pulling out on the handles and lifting it off.
- Disconnect the RJ45 cable from the display control board by pressing the tab and pulling the cable out.
- Remove the two screws at the bottom corners of the upper display panel, keeping the communication cable from being pulled.
- Remove the burner-end panel at the new display location.
- Set the upper display panel onto the top frame at the new location and secure it with screws.
- Move the cable clip to the 0.25 in. hole nearest the new display location.
- Plug the RJ45 connector back into the display control board.
- Reinstall the lower door panel by inserting the tabs and rotating it until the latches snap.
- Reinstall the non-display door panel by sliding it down onto the frames.
Remote 0-10 VDC modulation input
Weil-McLain · Ultra U-Control remote modulation
The U-Control accepts a remote 0-10 VDC signal on P15 terminal 6 (positive) and terminal 5 (common). The boiler starts above 1.0 VDC, shuts off below 0.5 VDC, stays at low fire until 2.0 VDC, then increases firing rate up to full input at 10.0 VDC. The control still monitors temperatures using the Priority 1 settings.
- Connect the positive 0-10 VDC wire to P15 terminal 6.
- Connect the signal common to P15 terminal 5.
- Set the boiler as Type 4 (SHADOW) if a separate controller is providing the signal.
Remote modulation 0-10V on/off points
Weil-McLain · SlimFit 1000-2000 Series 2 boilers
With 0-10V remote modulation, the boiler turns on at 0.9 VDC and off at 0.8 VDC. Voltage settings are fixed. 2 VDC equals 20% input and 10 VDC equals 100% input.
- Go to Contractor Menu, then Assign Inputs.
- Change Input 1 source to 0-10V.
- Note that the priority assigned to Input 1 cannot be used by another input.
Remote target 0-10V input setup
Weil-McLain · SlimFit 1000-2000 Series 2 boilers
A remote analog signal can set the supply temperature target. The priority must be set to 0-10V.
- Open the priority menu for the system.
- Set TARGET ADJUST to 0-10V.
- Set VOLTS FOR MIN for the desired minimum supply temperature.
- Set VOLTS FOR MAX for the desired maximum supply temperature.
- Assign Input 1 source to 0-10V if used.
- See Figure 56 in the manual for the target temperature versus voltage curve.
Replace flue gas temperature sensor after combustion test
Weil-McLain · All Ultra Series 4 models after combustion testing
A flue gas temperature sensor left out or badly seated can let flue gas spill into the boiler enclosure.
- Remove the rubber grommet from the probe.
- Insert the rubber grommet into the flue pipe.
- Insert the probe into the rubber grommet.
- Confirm the sensor is fully replaced before running the boiler.
Required and optional field wiring connections
Weil-McLain · SlimFit Series 2 field wiring
Required connections are 120 VAC power to the boiler, 120 VAC power out to the boiler circulator, and system supply and return sensors. Other connections depend on the system: call for heat from thermostat or end switch, zone circulators and valves, system circulator when needed, and outdoor sensor. Optional connections include external limits, interlocks such as combustion air damper or flow switch, 0-10 VDC modulation, remote alarm, additional heat demand contact, and MODBUS/BMS and boiler-to-boiler communication.
- Wire 120 VAC power to the boiler and the boiler circulator output.
- Connect the system supply and return temperature sensors.
- Wire thermostat, end switch or other call for heat inputs as the system requires.
- Add zone circulators, valves, relays, system circulator, or outdoor sensor where the system needs them.
- Add optional limits, interlocks, 0-10 VDC control, remote alarm, or communication wiring only as the system requires.
Reset the maintenance reminder after service
Weil-McLain · Evergreen Pro Series 2 boilers
Resets the maintenance reminder to the next service date.
- Open SERVICE > SERVICE INFO.
- Select Reset Reminder.
- Confirm that the Last Maintenance and Next Due dates updated.
Restriction on the economy/energy-saving override
Weil-McLain · CGi-25 to CGi-8 economy and reset control
Per the Energy Policy and Conservation Act, the boiler water temperature reduction feature has an override meant for external energy management systems. Do not use the override unless one of the listed conditions is true.
- Use the override only if an external energy management system reduces boiler water temperature as heating load falls.
- Use it only if the boiler is part of a modular or multiple boiler system with total input of 300,000 BTU/hr or more.
- Use it only if the boiler has a tankless coil.
- If none of these apply, leave the override off.
Return water temperature limit for standard single-zone piping
Weil-McLain · CGi-25 to CGi-8
Figures 15 and 16 apply only to single-zone systems designed for return water at least 130°F. Low return water temperature causes corrosion of sections and burners. Converted gravity and radiant systems need the special piping on pages 32 to 37.
- Confirm the system return water will stay at or above 130°F before using Figure 15 or 16.
- For converted gravity or radiant systems, use the low temperature piping methods on pages 32 to 37.
Rollout thermal fuse element has cut off gas flow
Weil-McLain · CGa, CGi, EG and PEG boilers
The rollout thermal fuse cuts gas flow if flame rollout occurs. The boiler must not be restarted until a service technician has checked it.
- Do not attempt to place the boiler in operation
- Call a service technician immediately
Rollout thermal fuse on EG-30 to EG-75
Weil-McLain · EG-30 through EG-75
The rollout thermal fuse element mounts on the front access panel for EG-30 through EG-75.
- Install the rollout thermal fuse element with the wire terminals facing up on the front access panel (Figure 40, page 49).
- Wire it per the appropriate wiring diagram.
Secure the boiler door after servicing
Weil-McLain · Ultra 80, 105, 155, 230, 299, 399
The door must be fastened to stop the boiler drawing air from the boiler room, which matters most when other appliances share the room.
- Reinstall the boiler door after servicing and fasten it securely.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.