Commissioning: Heat Pump tips (part 5 of 5)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on commissioning for heat pump. Check each one against the manual for your exact model before acting.

Remove ground loop caps before connecting

Viessmann · Vitocal 100-WA

Ground loop connections ship with caps fitted. The caps must be removed before the loop is connected.

  1. Remove the caps from the ground loop connections.
  2. Connect supply and return to the ground loop.

Route connection pipe to prevent rain entering indoor unit

Viessmann · Outdoor unit mounted above indoor unit

If the outdoor unit is higher than the indoor unit, make a downward arc in the connection pipe before it enters the wall so rain drips off before reaching the indoor unit.

  1. Form a downward arc in the connection pipe before it enters the wall.
  2. Confirm rain drips off the pipe before the wall penetration.

Safe leak testing and lockout before service

Viessmann · DLCSRB outdoor units, sizes 06 to 36

Never use air or oxygen-containing gases for leak testing or running the compressor. Shut off and lock out the main disconnect before installing or servicing; there may be more than one disconnect.

  1. Lock out and tag every disconnect switch before working on the system.
  2. Use only nitrogen or other non-oxygen gases for leak testing.
  3. Never use air or oxygen-containing gases to pressurize or run refrigerant compressors.

Sizing and air distribution compatibility

Viessmann · Vitocal 100-WA

Select the heat pump model from an accurate heat loss or gain calculation for the building. Confirm the model is compatible with the connected air distribution system.

  1. Complete a heat loss or gain calculation for the building.
  2. Confirm the model is compatible with the air distribution system.

Sound and vibration isolation

Viessmann · Vitocal 100-WA

Heat pumps, pumps, blowers and fans make noise and vibration. Use flexible ducting or duct connectors to separate the equipment from the building. Place a shock-absorbing pad under the unit on hard floors such as concrete, which also reduces moisture damage.

  1. Use flexible ducting or duct connectors.
  2. Place a shock-absorbing pad under the heat pump on hard surfaces.

Stand-alone DHW tank: sensor and tempering valve

Viessmann · Indoor unit DHW storage tank connection

A stand-alone DHW tank needs the DHW sensor supplied with the heat pump plus field-supplied fittings. For a non-Viessmann tank, confirm with the tank maker that the Viessmann DHW sensor works with it. A temperature tempering valve in the DHW supply line is strongly recommended.

  1. Mount the DHW sensor in the sensor well following the tank instructions (Vitocell tanks).
  2. For a non-Viessmann tank, verify sensor operation with the tank manufacturer.
  3. Install a temperature tempering valve in the DHW supply line.

System example 1: direct and mixing heating circuits with buffer tank

Viessmann · Vitocal 100-AW AM2V indoor and outdoor units with buffer and DHW tank

Example layout with one direct-connected heating circuit, one mixing-valve heating circuit, a system buffer tank and a DHW storage tank. Components are labelled A to V in the manual legend, including outdoor sensor, room sensor, DHW sensor, heating circuit pumps, mixing valve and a wye strainer.

  1. Follow the legend to match each component letter to its function before piping.
  2. Place the system separation required for underfloor tubing without oxygen diffusion barrier, and use corrosion-resistant materials on the secondary side of the heat exchanger.

System example 2: direct and mixing circuits with fan coil

Viessmann · Vitocal 100-AW AM2V with fan coil

Same layout as example 1 with a fan coil added as component W. Uses the same buffer tank, DHW storage tank and component legend.

  1. Use the legend to identify the fan coil (W) and its connection to the buffer tank circuit.
  2. Apply the same system separation requirement for underfloor tubing and corrosion-resistant secondary-side materials.

Tighten water connections with two wrenches

Viessmann · Vitocal 100-WA

Hold the heat pump connector with one wrench so the pipe cannot twist, and tighten the fitting with the second. Without support, the internal piping can be damaged.

  1. Hold the heat pump connector with one wrench.
  2. Tighten the fitting or pipe with the second wrench.

Underfloor heating separation

Viessmann · Vitocal 100-AW AM2V system piping

Underfloor heating that uses non-oxygen diffusion barrier tubing must be separated from the system. All components on the secondary side of the heat exchanger must be corrosion-resistant.

  1. Separate underfloor heating that uses non-oxygen diffusion barrier tubing.
  2. Use corrosion-resistant materials for all secondary-side components.

Unit selection sizing

Viessmann · All D5CSRA systems

Pick equipment that matches or slightly exceeds the expected peak load. This gives better humidity control, fewer cycles and less part-load running. In spaces with high sensible loads, size on the unit sensible load instead of the total load, and adjust for the room wet-bulb temperature so the unit is not undersized.

  1. Size on peak load, rounding slightly up.
  2. For high sensible-load rooms, size on sensible load.
  3. Adjust for the expected room wet-bulb temperature.

Fabricated manifold requirements

Weil-McLain · ECO HP heat pump with installer-built manifold

If the Easy-Up Manifold is not used, the installer-built manifold must have a heat trap, a Y-strainer, a circulator with its check valve, and common piping of 1 inch or larger.

  1. Make the vertical distance from the closely spaced system tees to the first elbow on the heat pump piping at least 2 inches.
  2. Install a Y-strainer with an 80 mesh screen, oriented flow down or horizontal.
  3. Install the heat pump circulator and fit its internal flow check valve before installing the circulator.
  4. Use 1 inch or larger common system piping.

Install an 80 mesh Y-strainer before the heat pump inlet

Weil-McLain · ECO HP heat pump

A Y-strainer with an 80 mesh screen is required ahead of the heat pump inlet to prevent early failure of the plate heat exchanger. Its flow direction must be down or horizontal.

  1. Install an 80 mesh Y-strainer before the ECO HP inlet.
  2. Orient the strainer so flow is down or horizontal.

Pipe the heat pump in an isolation loop with a heat trap

Weil-McLain · ECO HP heat pump

The ECO HP must be piped in an isolation loop off the system distribution piping, and a heat trap must be installed. Connections are 1 inch NPT and the header is 1-1/4 inch. Support all piping.

  1. Tee the heat pump loop off the system distribution piping as an isolation loop.
  2. Install a heat trap in the loop.
  3. Use 1 inch NPT connections at the heat pump and a 1-1/4 inch header.
  4. Support all piping adequately.

Use the supplied circulator only in the heat pump loop

Weil-McLain · ECO HP heat pump

The circulator supplied with the ECO HP is for the heat pump loop only. System, zone and DHW circulators must be supplied by the installer.

  1. Use the supplied circulator only in the heat pump loop.
  2. Provide separate system, zone and DHW circulators.

Water quality requirement

Weil-McLain · ECO HP heat pump

System water must meet the water quality requirements given on page 59. Poor water quality can cause heat pump failure or unreliable operation.

  1. Check that system water meets the water quality requirements on page 59 before startup.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.