Daikin Water Heater: Set cascade unit address
Set cascade unit address on a Daikin water heater: Assign a unique address to each cascade unit using the push buttons on the cascade unit's 7-segment display.
Applies to: Cascade units
How to fix set cascade unit address: step by step
- Power on the heat source unit, cascade unit and tank control board.
- Open the upper front panel of the cascade unit and the electrical component box service cover.
- In normal mode, hold the page break button (BS1) for more than 5 seconds to enter setting mode.
- Press the operation button (BS2) 13 times until the display shows the address table, then press the confirmation button (BS3).
- Use BS2 to select the address (1 to 8), then press BS3 to save. The display stops blinking and stays lit.
- Press BS3 again, then press BS1 to finish address setting.
- If confused, press BS1 to return to normal mode and start again from step 1.
- Close the service cover. Repeat for every cascade unit, numbering in ascending order with no duplicates.
If the unit shows an error code, look it up: Daikin Water Heater codes
Source: Mega-Q installation manual, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.