Daikin Water Heater: Keep R410A refrigerant piping clean, dry and tight
Keep R410A refrigerant piping clean, dry and tight on a Daikin water heater: R410A is very sensitive to moisture, dust and oil. The system must be kept clean, dry and leak free.
Applies to: Field refrigerant piping on R410A side
Common causes of keep r410a refrigerant piping clean, dry and tight
- Moisture or dust in the piping.
- Mineral oil or flux contaminating the refrigerant oil.
- Oxide scale forming inside pipes during brazing.
How to fix keep r410a refrigerant piping clean, dry and tight: step by step
- Keep moisture and dust out of the piping. Pinch the pipe ends if the work lasts a month or longer, or pinch or tape them if it lasts less than a month.
- Take extra care when passing pipes through walls or holes to the outside.
- Do not use flux when brazing. Use phosphor copper filler B-Cu93P-710/795.
- Flush the pipe with nitrogen during brazing and use a pressure reducing valve set to about 3 psi (0.02 MPa).
- Do not use antioxidants when brazing.
- Charge R410A only in liquid form, because it is a blend.
- Do not use gauges, hoses, leak detectors or recovery equipment designed for conventional refrigerants.
If the unit shows an error code, look it up: Daikin Water Heater codes
Source: Daikin Mega-Q installation manual, p. 11-12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.