Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Daikin Water Heater: Drainage and freeze protection on site

Updated · by Aurora Star Tech Inc.

Drainage and freeze protection on site on a Daikin water heater: Water drains from the bottom frame during operation and defrost. Cold outdoor temperatures can freeze the bottom frame and foundation.

Homeowner with a heating or cooling system problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Heat source unit and cascade unit

Common causes of drainage and freeze protection on site

  • Condensation and defrost water drop through gaps in the bottom frame.
  • Ground below freezing for long periods can freeze the bottom frame.

How to fix drainage and freeze protection on site: step by step

  1. If drain water is a problem, use a stand and a field supplied drain pan.
  2. In areas that stay below freezing for long periods, attach a drain pan heater (sold separately) to the heat source unit.
  3. Leave a gap between the bottom frame and the foundation surface so frozen ground does not reach the frame. In cold regions the manual recommends 20 in. (500 mm) to 40 in. (1000 mm).
  4. Provide a drainage ditch around the foundation so water does not collect around the system.
  5. In areas where the outdoor air can drop below freezing, drain the water from inside the cascade unit before switching off the breaker.
  6. Do not turn off the power immediately after stopping operation. Wait at least 5 minutes before switching off the power, or water leakage can occur.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Water Heater codes

Source: Daikin Mega-Q installation manual, p. 9-10. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service