Daikin Heat Pump: Run system test and charge calculation (inverter systems)

Updated · by Aurora Star Tech Inc.

Run system test and charge calculation (inverter systems) on a Daikin heat pump: The system test is required for inverter systems. The app asks for the charge calculation before the test runs, using the measured line set length and the liquid and suction line diameters. Enter the actual charge weighed in.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Inverter systems using Daikin One Touch

How to fix run system test and charge calculation (inverter systems): step by step

  1. Measure the total line set length.
  2. Select the liquid and suction line diameter in the app.
  3. Calculate the required trim charge from the app.
  4. Enter the actual charge weighed in.
  5. Verify service valves are open.
  6. Tap "Run Test".
  7. Leave the screen if needed; the test keeps running and you can return later.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin One Touch Smart Thermostat Training Module TRC-10, pp. 29-30. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.