Daikin Heat Pump: Remove panels, side plates and terminal covers (3.5 to 5.0 ton)

Updated · by Aurora Star Tech Inc.

Remove panels, side plates and terminal covers (3.5 to 5.0 ton) on a Daikin heat pump: Take off the outdoor unit panels and covers in order, and disconnect the field wiring before removing the terminal board cover.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 3.5 to 5.0 ton HP & AC

How to fix remove panels, side plates and terminal covers (3.5 to 5.0 ton): step by step

  1. Remove 3 screws and take off the suction grille.
  2. Remove 9 screws and take off the top panel.
  3. Remove 1 screw and push down to remove front panel (2).
  4. Remove 8 screws and take off front panel (1).
  5. Remove 4 screws and take off the discharge grille.
  6. Remove 1 screw and take off the terminal board shield plate. This is a 3 class hex head tapping screw; reuse the same screw.
  7. Disconnect the external power supply, ground and communication wires.
  8. Remove 4 screws and take off the side cover.
  9. Remove 5 screws and take off the right side plate. The circled screws are 3 class hex head tapping screws; reuse the same screws.
  10. If connected, remove 2 screws and separate the conduit tube from the patch plate.
  11. Remove 1 screw and take off the field wiring plate. This is a 3 class hex head tapping screw; reuse the same screw.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin SiUS612209EA service instructions, pp. 105-108. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.