Daikin Heat Pump: Power circuit and field cable requirements
Power circuit and field cable requirements on a Daikin heat pump: Keep low voltage wiring separated from power wiring to prevent interference.
Applies to: Field wiring at heat source and cascade units
How to fix power circuit and field cable requirements: step by step
- Apply the rated voltage of 208/230 V.
- Install a main switch and a slow blow fuse on each phase.
- Keep low voltage wiring (remote controller and between units) at least 2 in. (50 mm) from power wiring.
- Secure power wiring to the power terminal block as described in section 7-4.
- Secure transmission wiring as described in section 7-3.
- Use clamps such as insulation lock ties so wires do not touch piping.
- Shape wires so the control box cover is not deformed, then close the cover firmly.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin Mega-Q installation manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.