Daikin Heat Pump: Outdoor unit PCB abnormality, code E1
Outdoor unit PCB abnormality, code E1 on a Daikin heat pump: The outdoor PCB microprocessor is not running correctly, or the zero-cross signal is not detected.
Applies to: Inverter pair wall mounted FTXM-W/V, outdoor unit
Common causes of outdoor unit pcb abnormality, code e1
- Defective outdoor unit PCB
- Noise
- Momentary voltage drop
- Momentary power failure
How to fix outdoor unit pcb abnormality, code e1: step by step
- Turn off the power switch before connecting or disconnecting any connector.
- Check whether the outdoor unit is grounded. If not, ground the system.
- Investigate the cause of noise. The cause may be external to the unit.
- Turn the power on.
- If the error returns, replace the outdoor unit PCB (main PCB).
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 116. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.