Daikin Heat Pump: Opening and closing the stop valves
Opening and closing the stop valves on a Daikin heat pump: Stop valves ship closed. They must be opened before start-up. Inadequate torque can leak refrigerant. The 3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity units use a back sealing type valve, so the back seal must be closed as in the opening procedure. Torque values are in the stop valve tables.
Applies to: Liquid and gas stop valves on DX6VS / DZ6VS / DZ6VSA units
Common causes of opening and closing the stop valves
- Stop valve left closed at start-up
- Insufficient tightening torque causing leakage
How to fix opening and closing the stop valves: step by step
- Remove the valve lid and turn the valve counterclockwise with a hex wrench to open.
- Turn until the shaft stops.
- Then turn until the designated torque is reached, as in the stop valve table.
- Refit the valve lid.
- To close, remove the valve lid and turn clockwise until the shaft stops.
- Then tighten to the designated torque, and refit the valve lid.
- On back-sealing valves, seal the back seal as in opening step 3.
- Make sure both liquid and gas stop valves are open before start-up.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.