Main circuit short check (Check No.20) on a Daikin heat pump: Checks the diode bridge DB1 for a short on the main circuit. Confirm the DC voltage is about 0 V before testing.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Outdoor unit main circuit / diode bridge DB1

Common causes of main circuit short check (check no.20)

  • Short circuit on the main circuit

How to fix main circuit short check (check no.20): step by step

  1. Confirm the voltage between (+) and (-) of diode bridge DB1 is about 0 V before checking.
  2. Measure the resistance between the DB1 pins in both polarities using the table in the manual.
  3. If the resistance is normal (several kΩ to several MΩ), the main circuit is OK.
  4. If the resistance is very low (about 1 kΩ or less, per the manual), a short circuit is present on the main circuit.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin Inverter Pair FTXM-W/V service manual, p. 154. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.