Daikin Heat Pump: Main circuit short check (Check No.20)
Main circuit short check (Check No.20) on a Daikin heat pump: Checks the diode bridge DB1 for a short on the main circuit. Confirm the DC voltage is about 0 V before testing.
Applies to: Outdoor unit main circuit / diode bridge DB1
Common causes of main circuit short check (check no.20)
- Short circuit on the main circuit
How to fix main circuit short check (check no.20): step by step
- Confirm the voltage between (+) and (-) of diode bridge DB1 is about 0 V before checking.
- Measure the resistance between the DB1 pins in both polarities using the table in the manual.
- If the resistance is normal (several kΩ to several MΩ), the main circuit is OK.
- If the resistance is very low (about 1 kΩ or less, per the manual), a short circuit is present on the main circuit.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin Inverter Pair FTXM-W/V service manual, p. 154. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.