Updated · by Aurora Star Tech Inc.

Compressor overload (OL activation), code E5 on a Daikin heat pump: Compressor overload is detected through the compressor OL. The system shuts down if the error repeats. Reset occurs after about 60 minutes of continuous run without another error. OL (Q1M) activating temperature is 120 to 130°C (248 to 266°F). Recovery temperature is 105°C (221°F).

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Inverter pair wall mounted FTXM-W/V, compressor overload circuit

Common causes of compressor overload (ol activation), code e5

  • Discharge pipe thermistor disconnected or defective
  • Connector S40 disconnected
  • Two terminals of OL (Q1M) disconnected
  • Defective OL (Q1M) or broken OL harness
  • Defective electronic expansion valve or coil
  • Defective four way valve or coil
  • Defective outdoor unit PCB
  • Refrigerant shortage
  • Water mixed in refrigerant
  • Defective stop valve

How to fix compressor overload (ol activation), code e5: step by step

  1. Turn off the power switch before connecting or disconnecting any connector.
  2. Check whether the discharge pipe thermistor is disconnected. If so, insert it in position. If the thermistor is faulty, replace it. See Check No. 01 (P.141).
  3. Check that connector S40 is properly connected. If not, reconnect it.
  4. Disconnect connector S40 from the PCB and measure the resistance across its two terminals. Nearly 0 Ω is normal.
  5. Disconnect the two terminals of OL (Q1M) and measure its resistance. Nearly 0 Ω is normal. If faulty, replace the OL (Q1M) or the OL harness.
  6. Check the electronic expansion valve. See Check No. 12 (P.143). Replace the valve or its coil if faulty.
  7. Check the four way valve. See Check No. 13 (P.144). Replace the valve or its coil if faulty.
  8. Check the refrigerant line for shortage, water contamination and stop valve position. See Check No. 14 (P.145). Correct any refrigerant shortage, water mixed in refrigerant or closed stop valve.
  9. If all checks are normal, replace the outdoor unit PCB (main PCB).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 118. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.