Daikin Heat Pump: Checking compressor efficiency
Checking compressor efficiency on a Daikin heat pump: Low efficiency means the compressor cannot pump vapor properly. Confirm the charge is correct before condemning the compressor.
Applies to: Outdoor unit compressor
Common causes of checking compressor efficiency
- Broken or damaged compressor
How to fix checking compressor efficiency: step by step
- Attach gauges to the high and low sides.
- Start the system and run CHARGE MODE.
- If the readings show low high-side pressure, high low-side pressure, low temperature difference across the coil, and low compressor amp draw, and the charge is correct, replace the compressor.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.