Daikin Heat Pump: Check thermistor, EEV coil and solenoid valve coil resistance (S-26)
Check thermistor, EEV coil and solenoid valve coil resistance (S-26) on a Daikin heat pump: Outdoor units and EEV indoor units use thermistors for outdoor air, coil, liquid, discharge, defrost, suction, indoor gas and indoor liquid. The EEV and solenoid valves are coils that also have a resistance check.
Applies to: Outdoor units and EEV indoor units
Common causes of check thermistor, eev coil and solenoid valve coil resistance (s-26)
- Open, shorted or out-of-range thermistor
- Open or shorted EEV coil
- Open or shorted solenoid valve coil
How to fix check thermistor, eev coil and solenoid valve coil resistance (s-26): step by step
- Disconnect power to all equipment.
- Disconnect the thermistor connector from the control board.
- Connect an ohmmeter across the thermistor terminals and compare with the thermistor resistance table. Replace if open, shorted or out of range.
- To check the EEV coil, disconnect the EEV cable from the control board and read resistance between the connector pins. The reading should be 40 to 50 Ω.
- To check the solenoid valve coil, disconnect the cable from the control board and read resistance between the connector pins. The reading should be 1,480 to 1,820 Ω.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin SiUS612209EA service instructions, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.