Daikin Heat Pump: Check indoor or outdoor pressure sensor
Check indoor or outdoor pressure sensor on a Daikin heat pump: The outdoor and indoor pressure sensors read low or high side pressure as a DC output voltage. The voltage-versus-pressure curve is a graph in the manual and its values are not listed as text here.
Applies to: Outdoor units 1.5-3.0 ton and 3.5-5.0 ton; indoor units
Common causes of check indoor or outdoor pressure sensor
- Sensor open or shorted
- Output voltage outside the valid range
How to fix check indoor or outdoor pressure sensor: step by step
- Turn power ON and note that line voltage is present.
- Connect a voltmeter across the sensor terminals between the black and white wires.
- Compare the reading with the voltage versus pressure characteristic for the unit (1.5 to 3.0 ton or 3.5 to 5.0 ton and indoor unit).
- Replace the sensor if it is open, shorted or outside the valid voltage range.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin SiUS612209EA service instructions, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.