Updated · by Aurora Star Tech Inc.

Set up proof of closure for a flow switch or combustion air damper on a Weil-McLain boiler: Proof of closure must be wired with isolated contacts. The P7 circuit carries 5 VDC. The blower will not start until the switch is closed.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SlimFit 550/750 Series 3 boiler

Common causes of set up proof of closure for a flow switch or combustion air damper

  • Proof of closure open after the 4-minute window
  • Proof of closure opens during firing

How to fix set up proof of closure for a flow switch or combustion air damper: step by step

  1. Clip only the purple wire on P7 pin 3 to make room for the field wiring. Do not clip any other P7 wire.
  2. Strip the jumper ends and wire the devices as shown in Figure 52.
  3. Connect the right side of each jumper only to the right side of other jumpers.
  4. For a combustion air damper, set Input 3 as AUX PUMP/OUTPUT.
  5. Set the AUX PUMP/OUTPUT operating mode to ANY BURNER DEMAND.
  6. Connect Output 3 (120 VAC) to the damper motor. Use an isolation relay if the damper needs another voltage or more than 2.2 A.
  7. A flow switch needs no control settings.
  8. Expect 4 minutes for the switch to close after a call. If it stays open, or opens during firing, the control locks out and clears when the switch closes again.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SlimFit Series 3 boiler manual, p. 55. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.