Weil-McLain Boiler: Set up a variable speed boiler pump (0-10 Vdc output)
Set up a variable speed boiler pump (0-10 Vdc output) on a Weil-McLain boiler: Connect the control 0-10 Vdc output to the pump 0-10 Vdc input and set the pump voltages from the manual test screen.
Applies to: Variable speed boiler pump on 0-10 Vdc output
How to fix set up a variable speed boiler pump (0-10 vdc output): step by step
- Connect the boiler 0-10 Vdc output to the 0-10 Vdc input of the pump.
- From the Contractor menu go to Diagnostics, then Manual Test Mode.
- Highlight FORCE RATE, select EDIT, use the arrows to set HIGH, then press SAVE.
- Adjust the pump voltage to the desired boiler delta T and press SAVE AS MAX VOLTS.
- Set Pump Volts back to AUTO to edit FORCE RATE again.
- Repeat for each FORCE RATE speed, including ignition speed. Ignition speed sets the voltage to the pump when the burner is not active.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 boiler manual, p. 87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.