Weil-McLain Boiler: Set bypass valves for primary/secondary low temperature piping
Set bypass valves for primary/secondary low temperature piping on a Weil-McLain boiler: Valve 7a mixes hot boiler outlet water with cooler return water. Valve 7b controls flow through the boiler secondary loop. Set them so the boiler return water is at least 130°F. Set the valves with the system cool, for the coldest expected water temperature (usually 60°F).
Applies to: CGi-25 to CGi-8
Common causes of set bypass valves for primary/secondary low temperature piping
- Return water below 130°F
How to fix set bypass valves for primary/secondary low temperature piping: step by step
- Set the valves while the system is cool, for the coldest expected water temperature (usually 60°F).
- Start with valve 7a fully closed and valve 7b fully open.
- Slowly open valve 7a while closing valve 7b.
- Stop when gauge 8 reads 130°F while gauge 4a reads 60°F.
- If gauge 8 is not available, adjust until the boiler-mounted gauge reads at least 150°F with cold system return water (about 60°F).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 boiler manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.