Weil-McLain Boiler: Purge air from the water system
Purge air from the water system on a Weil-McLain boiler: Air is removed zone by zone through the purge valve, then the remaining air vents are opened.
Applies to: SlimFit Series 2 startup
Common causes of purge air from the water system
- Air trapped in zones or at high points
How to fix purge air from the water system: step by step
- Connect a hose to the purge valve and route it to a drain where flow can be seen.
- Close the boiler or system isolation valve between the purge valve and the fill connection.
- Close the zone isolation valves.
- Open the quick-fill valve on the cold make-up line and open the purge valve.
- Open one zone isolation valve at a time and run water until no air flow is seen. Close it and move to the next zone.
- Close the quick-fill and purge valves, remove the hose, and open all isolation valves.
- Watch the system pressure rise to the correct cold-fill pressure.
- If no purge valves are installed, open manual vents one at a time from the lowest floor until water squirts out.
- Open the automatic air vent one turn on diaphragm or bladder tank systems.
- Refill to the correct pressure.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual, p. 79. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.