Weil-McLain Boiler: Nothing on display and no other components running (no 120 V)
Nothing on display and no other components running (no 120 V) on a Weil-McLain boiler: Control is not receiving 120 V power.
Applies to: SlimFit 1000-2000 Series 2
Common causes of nothing on display and no other components running (no 120 v)
- Service switch or breaker off
- Power supply problem to service switch
- Wiring fault inside control pod
- Blown 12-amp fuse
How to fix nothing on display and no other components running (no 120 v): step by step
- Check the service switch and/or circuit breaker is on.
- Check for 120 VAC at the service switch; troubleshoot the supply if absent.
- Check for 120 VAC at the line voltage terminal block in the top left electrical compartment.
- Correct wiring inside the control pod per the wiring diagram.
- Inspect the 12-amp fuse (see page 94) and replace with the proper part if needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 97. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.