Weil-McLain Boiler: Direct exhaust vertical vent termination: location and clearances
Direct exhaust vertical vent termination: location and clearances on a Weil-McLain boiler: Clearances for a vertical (roof) direct exhaust termination. The vent must end in a coupling, and all clearances must be met for the roof, walls, openings and air inlets.
Applies to: SF-550 and SF-750 direct exhaust, vertical termination
Common causes of direct exhaust vertical vent termination: location and clearances
- Termination too low on the roof or too close to a snow line
- Termination in a recessed area or near a forced air intake
How to fix direct exhaust vertical vent termination: location and clearances: step by step
- Terminate at least 12 in above the roof or snow line, as shown in the figure.
- Keep it at least 6 ft from adjacent walls.
- Keep it at least 5 ft below any roof overhang.
- Keep it at least 3 ft above any forced air intake within 10 ft.
- Keep it at least 48 in below or horizontally from any door, window or other gravity air inlet.
- Keep it at least 4 ft horizontally from electric meters, gas meters, regulators, relief valves or other equipment.
- End the vent piping in a coupling with a bird screen fitted.
- Keep the termination away from wind eddies, building corners, adjacent surfaces and recessed areas.
- Locate or guard the vent so condensate does not damage exterior finishes.
- Do not extend exposed vent pipe beyond the length shown in the figure.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 34-35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.