Constant makeup water, black water or popping noise (water boiler) on a Weil-McLain boiler: Boiler needs water often, water is black, or the block pops and percolates.
Applies to: WGO-2 to WGO-9 oil-fired water boilers
Common causes of constant makeup water, black water or popping noise (water boiler)
- Leaks in the boiler or piping
- Mineral build-up in the sections from fresh makeup water
- Oxygen corrosion from leaks
- Water pH outside 7.0 to 8.5
How to fix constant makeup water, black water or popping noise (water boiler): step by step
- Find and fix leaks first.
- Check pH. Keep it between 7.0 and 8.5.
- If the block pops, de-lime it after the leaks are fixed.
- Do not use petroleum-based stop-leak in the system.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, Troubleshooting p.7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.