Weil-McLain Boiler: Clean the aluminum heat exchanger (water side)
Clean the aluminum heat exchanger (water side) on a Weil-McLain boiler: The heat exchanger is cast aluminum, so use only the approved cleaner. Trisodium phosphate (TSP) must not be used in systems containing aluminum because its high pH removes the protective oxide layer and shortens heat exchanger life.
Applies to: SlimFit SF-550 and SF-750 Series 3 with aluminum heat exchanger
How to fix clean the aluminum heat exchanger (water side): step by step
- Do not use trisodium phosphate (TSP) or any cleaner with a similar high pH.
- Use ONLY WM Technologies Sentinel X400 cleaner.
- Order the cleaner using the replacement parts section.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 105. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.