Weil-McLain Boiler: Circulator zoning with primary/secondary piping
Circulator zoning with primary/secondary piping on a Weil-McLain boiler: Each zone has its own circulator and the boiler loop runs as a secondary off the primary system loop. Optional DHW piping can be added.
Applies to: SF-550 and SF-750
How to fix circulator zoning with primary/secondary piping: step by step
- Install a separate circulator for each zone, sized for the flow and head needed.
- Fit a flow/check valve on the boiler outlet to stop gravity circulation during DHW heating.
- Pipe the boiler loop at least to the minimum size in Figure 4 (p. 13).
- Provide an expansion tank per p. 14. No closed-type tank if the DHW heater has an automatic vent.
- For a DHW tank wired as a zone, the tank must not already be connected to the boiler. Set the Advanced Manual parameters so the boiler circulator runs on DHW calls and TARGET MOD SENSOR is System Supply.
- Choose a DHW priority scheme: DHW priority, space heating priority, or no priorities (only when DHW is a zone; do not use outdoor reset in that case).
- The boiler circulator cannot be used as a zone pump. For more than 3 zones, use the WMCR zone circulator controller.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.