Weil-McLain Boiler: Check water chemistry and inhibitor at least yearly
Check water chemistry and inhibitor at least yearly on a Weil-McLain boiler: Water and inhibitor are checked after fill and once a year to prevent corrosion.
Applies to: SlimFit Series 2 annual maintenance
Common causes of check water chemistry and inhibitor at least yearly
- Low pH or low inhibitor level
- Antifreeze concentration too low
How to fix check water chemistry and inhibitor at least yearly: step by step
- After fill and leak test, check pH and chlorine.
- Verify antifreeze concentration if it is used.
- Test a water sample for pH. It must be 7.0 to 8.5, or use the Sentinel test kit to check inhibitor concentration.
- If pH is out of range or the test kit shows low inhibitor, correct it.
- Test antifreeze concentration at least annually. If it is low, add antifreeze or drain and refill with the correct mix.
- Check the inhibitor level again after any adjustment.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.