Weil-McLain Boiler: Annual startup: inspect flame sense assembly
Annual startup: inspect flame sense assembly on a Weil-McLain boiler: The flame sensor is the shorter rod with a pink ceramic insulator. It mounts on the piping end section.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of annual startup: inspect flame sense assembly
- White oxide buildup on the sense rods
- Damaged gasket or harness
- Flame sensor in the wrong location
How to fix annual startup: inspect flame sense assembly: step by step
- Remove the flame sensor assembly from the piping end section of the heat exchanger.
- Remove white oxides from the sense rods with steel wool. If they cannot be cleaned well, replace the assembly.
- Reinstall with the gasket in good condition and correctly positioned. Replace the gasket if needed.
- Inspect the flame sense harness and connections. Replace as needed.
- Confirm the flame sensor is on the piping end, not the burner end.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 90. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.