Weil-McLain Boiler: Annual startup: inspect and clean the air inlet box screen
Annual startup: inspect and clean the air inlet box screen on a Weil-McLain boiler: Check the air inlet screen for debris. In direct vent installs, the air inlet box is reached by removing the cover on the air pipe inspection tee.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of annual startup: inspect and clean the air inlet box screen
- Debris or contaminants collected on the air inlet screen
How to fix annual startup: inspect and clean the air inlet box screen: step by step
- On direct vent installs, remove the cover from the air pipe inspection tee, or remove air piping as needed to reach the inlet box.
- If you cannot see straight down into the inlet box, use an inspection mirror.
- Inspect the air inlet screen thoroughly.
- Vacuum off any debris. Use a soft brush if needed to loosen material.
- On direct vent installs, reinstall the cover on the air pipe tee when finished.
- On direct exhaust installs, inspect and clean the screen as needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.