Riello Boiler: Riello 40 F5 start-up settings on Ultra Oil boilers
Riello 40 F5 start-up settings on Ultra Oil boilers on a Riello boiler: Starting settings from the Weil-McLain set-up chart. Final set-up must be done with a combustion analyzer.
Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5
How to fix riello 40 f5 start-up settings on ultra oil boilers: step by step
- UO-3 at 0.80 GPH: Delavan 0.65 x 70B nozzle, 150 psi, turbulator 0, air gate 2.75.
- UO-3 at 1.00 GPH: 0.85 x 60B nozzle, 145 psi, turbulator 1, air gate 2.8.
- UO-4 at 1.20 GPH: 1.00 x 70B nozzle, 145 psi, turbulator 3, air gate 2.9.
- UO-5 at 1.40 GPH: 1.10 x 70B nozzle, 160 psi, turbulator 4, air gate 2.9.
- All: 8 in. air tube, 4-1/4 in. insertion. End cone must sit at least 1/4 in. back from the inside face of the chamber refractory.
- Pump pressure range on this burner is 130 to 200 psig.
- Take final readings with the burner cover on. Readings change when the cover is off.
Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Burner adjustment table p.12; Technical data p.2; Mounting p.4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.