Beckett Boiler: NX burner: start-up settings on Ultra Oil boilers

Updated · by Aurora Star Tech Inc.

NX burner: start-up settings on Ultra Oil boilers on a Beckett boiler: Nozzle, pump pressure and head/air starting points for each Ultra Oil size. The NX is shipped set for 1.00 GPH on the UO-3.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Beckett NX burners on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)

Common causes of nx burner: start-up settings on ultra oil boilers

  • Wrong nozzle or pressure for the boiler size
  • UO-3 changed to 0.80 GPH without the other changes

How to fix nx burner: start-up settings on ultra oil boilers: step by step

  1. UO-3 CV (spec WL6403) and UO-3 DV (WL6503), air tube NX70LC, 1-3/4 in. insertion.
  2. UO-3 at 0.80 GPH: nozzle 0.65 x 60 A (Delavan) or 0.65 x 60 B (Hago), 150 psig, head/air 3.50 (CV) or 3.25 (DV).
  3. UO-3 at 1.00 GPH: nozzle 0.75 x 60 B (Hago or Delavan), 175 psig, head/air 4.00 (CV) or 3.75 (DV).
  4. UO-4 CV (WL6404) and DV (WL6504), 1.20 GPH, air tube NX90LD, 3-1/2 in. insertion: nozzle 1.00 x 60 W (Delavan) or 1.00 x 60 AB (Danfoss), 140 psig, head/air 2.50.
  5. UO-5 CV (WL6405) and DV (WL6505), 1.40 GPH, NX90LD, 3-1/2 in.: nozzle 1.10 x 70 B (Hago or Delavan), 160 psig, head/air 2.50.
  6. Going to 0.80 GPH on a UO-3: change the nozzle, set pump pressure and head/air from the list, and lay the 14 x 16 in. blanket on the combustion chamber floor.
  7. All direct vent (DV) boilers need the combustion chamber blanket (comes with the burner).
  8. Pump pressure is above 100 psig, so the real firing rate is higher than the number stamped on the nozzle (1.00 GPH at 140 psig is about 1.18 GPH).
  9. Head/air numbers are starting points only. Final setting with an analyzer.
  10. Check the burner spec number on the carton against this list before firing. Nozzle columns in the text export were split across lines: confirm against Table 1 p.4-5.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Beckett Boiler codes

Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Table 1 Burner Configurations p.4-5; nozzle flow note p.18. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.