Beckett Boiler: NX burner: annual service checklist

Updated · by Aurora Star Tech Inc.

NX burner: annual service checklist on a Beckett boiler: Yearly service list for the NX. Power off before working on it.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)

Common causes of nx burner: annual service checklist

  • Annual service due
  • Dusty or dirty room (service more often)

How to fix nx burner: annual service checklist: step by step

  1. Turn off power to the burner. Remove the cover (four thumb screws).
  2. Replace the oil line filter cartridge. Clean the pump strainer if it has one. Check all oil fittings for leaks and the lines for water or sludge.
  3. Pull the nozzle line (disconnect connector tube, release igniter clips, open rear door, loosen splined nut). Replace the nozzle; hold the adapter with a 3/4 in. wrench, tighten with 5/8 in. Do not over-tighten.
  4. Clean and check electrodes; replace if cracked, chipped or rounded tips. Check electrode tip settings and igniter spring contacts.
  5. Clean the cad cell lens. Make sure the low firing rate baffle is in place if the setup needs it.
  6. Clean the blower wheel, air inlet, air guide, retention head, throttle cup and throttle ring. Clean the throttle cup sight windows gently.
  7. Check gaskets, motor amps (not above nameplate) and wiring.
  8. Check pump pressure and cutoff, primary control lockout timing and ignition.
  9. Clean the boiler flue passages, flue pipe and chimney. Replace corroded pipe.
  10. Set combustion with an analyzer and record the readings.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Beckett Boiler codes

Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Trained service technician's regular maintenance p.16-18. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977