Updated · by Aurora Star Tech Inc.

AFG burner: air in the oil line, priming the pump (SYS light yellow) on a Beckett boiler: After a new install, filter change or running out of oil, the pump needs to be bled. The GeniSys 7565 primary on the AFG has a 4-minute Pump Prime mode for long purges.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Beckett AF/AFG oil burners (0.40-3.00 GPH) on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers

Common causes of afg burner: air in the oil line, priming the pump (sys light yellow)

  • Air in the oil supply line or pump
  • Oil tank ran empty
  • New install or filter/strainer just changed

How to fix afg burner: air in the oil line, priming the pump (sys light yellow): step by step

  1. Before any start or reset: make sure there is no oil or oil vapor in the appliance. If the chamber is flooded, shut off power and oil and clean out the oil first. If it is full of vapor, let it cool and air out.
  2. Never bleed the pump with oil spraying into a hot chamber. Put a gauge on the nozzle port or fully open the bleed valve.
  3. Open the oil supply valves. Close the air band and partly open the air shutter for the bleed only.
  4. Call for heat. When the burner starts, hold the ACTION button about 15 seconds until SYS turns yellow, then let go. The burner restarts.
  5. While the igniter is still on, tap ACTION once. The control goes into Pump Prime: motor, igniter and valve run for 4 minutes and SYS stays solid yellow.
  6. Open the bleed fitting and run oil into a container until there are no bubbles or froth, then tighten it.
  7. After 4 minutes SYS goes green and the control returns to standby.
  8. Set the pump pressure to the appliance maker's number, then set combustion with instruments.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Beckett Boiler codes

Source: Beckett AF/AFG Burner Manual for Weil-McLain WGO/WTGO/SGO boilers (550-143-079/1224), Start up burner, p.14-15; same in Beckett AFG Burner Manual for Weil-McLain Ultra Oil boilers (0225). Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.