Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Daikin Air Handler: Recall the last six faults on the EEV indoor unit

Updated · by Aurora Star Tech Inc.

Recall the last six faults on the EEV indoor unit on a Daikin air handler: Use the FAULT RECALL button on the control board to step through the six most recent faults. The unit must be in standby (no thermostat inputs). Repeated identical faults show a maximum of three times. The recall times out after 3 minutes idle.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EEV indoor units (control board 7-segment display). Active codes of the gas furnace or blower are on their own boards.

How to fix recall the last six faults on the eev indoor unit: step by step

  1. Confirm the control is in standby with no thermostat inputs.
  2. Press FAULT RECALL for 2 to 5 seconds until the display shows solid "--".
  3. Release the button. The display shows the most recent fault.
  4. Press FAULT RECALL again to step to older faults.
  5. At the end of the list the display shows "--" and returns to standby.
  6. Holding the button longer than 15 seconds returns the control to standby.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Air Handler codes

More service & test modes tips for air handler

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 25. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Air Handler Emergency

647-657-2977