Daikin Air Handler: No 24 VAC control voltage from indoor transformer
No 24 VAC control voltage from indoor transformer on a Daikin air handler: The indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary). The outdoor section has no transformer. Use this check when the control circuit has no 24 V.
Applies to: Indoor unit transformer, 24 V control circuit
Common causes of no 24 vac control voltage from indoor transformer
- Faulty transformer
- Bad wiring or splices
- No line voltage at the transformer primary
How to fix no 24 vac control voltage from indoor transformer: step by step
- Disconnect power, remove the control panel cover to reach the transformer, then restore power for measurement.
- With power on, measure voltage across the transformer secondary (R to C).
- If there is no voltage, check the wiring and splices.
- Check primary voltage at the incoming line connections or splices.
- If line voltage is present at the primary and the wiring is good, replace the transformer.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.