Daikin Air Handler: Measuring total external static pressure on a two-piece indoor unit
Measuring total external static pressure on a two-piece indoor unit on a Daikin air handler: For an EEV cased coil paired with a gas furnace or modular blower, add the return and supply static readings to get total external static. Use the airflow chart of the furnace or blower to find CFM at that static.
Applies to: Two-piece EEV cased coil with gas furnace or modular blower
How to fix measuring total external static pressure on a two-piece indoor unit: step by step
- Install clean filters in the indoor unit.
- With a draft gauge (inclined manometer or Magnehelic), measure return static at the inlet of the furnace or modular blower. This reading is negative (example: -0.30 inH2O / -74.7 Pa).
- If a filter is installed with the furnace, measure return static between the filter and the furnace.
- Measure supply static at the outlet of the furnace or modular blower. This reading is positive (example: 0.20 inH2O / 49.8 Pa).
- Add the absolute values of the two readings for total external static (example: 0.30 + 0.20 = 0.50 inH2O, or 124.5 Pa).
- Include any electronic air cleaner in the readings if one is used.
- Read CFM from the furnace or blower airflow chart at the measured static.
- If static is above the maximum or below the minimum allowed, check for closed dampers or registers and for undersized, oversized or poorly laid out ductwork.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.