Daikin Air Handler: Emergency heating mode for EEV cased coil with gas furnace or modular blower
Emergency heating mode for EEV cased coil with gas furnace or modular blower on a Daikin air handler: Use only as a temporary fix when wiring or the thermostat cannot be corrected at once. The gas furnace or modular blower runs the electric heat without the thermostat. Emergency mode does not hold a room set point. Acceptable when the outdoor unit shows E51 or Ed2, or the EEV indoor unit shows E76, E77 or E78. Cycling power may clear codes without fixing the cause.
Applies to: EEV cased coil with gas furnace or modular blower
How to fix emergency heating mode for eev cased coil with gas furnace or modular blower: step by step
- Turn off power to all equipment before setting or wiring.
- Remove the thermostat communication wires (1, 2, R and C) from all connected equipment (EEV cased coil, gas furnace or modular blower, outdoor unit and thermostat).
- Short-circuit the communication terminal of the gas furnace or modular blower with the wires so it runs alone in heating emergency mode. Check the furnace or blower service manual for the connection points.
- Set the EEV cased coil dip switches S-21 to OFF and S-22 to ON on switch bank DS-6.
- Turn on power. Heating emergency mode starts. The outdoor unit must stay off during this mode. No dip switch change is needed in the outdoor unit.
- When communication is restored, set the dip switches back to default and restore all thermostat communication wires.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.