Daikin Air Handler: ECM motor winding check

Updated · by Aurora Star Tech Inc.

ECM motor winding check on a Daikin air handler: Checks the three motor phase windings for balance and for shorts to the motor shell.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECM blower motor windings

Common causes of ecm motor winding check

  • Unequal or open phase windings
  • Phase winding shorted to motor shell

How to fix ecm motor winding check: step by step

  1. Disconnect power and wait 5 minutes for capacitors to discharge.
  2. Disassemble the motor as in the control/end bell steps.
  3. At the 3-circuit motor harness, measure resistance between each phase winding. Readings should be equal.
  4. Replace the motor if readings are unequal, open, or shorted.
  5. Measure resistance between each phase winding and the motor shell. Replace the motor if any winding is shorted to the shell.
  6. Reassemble and reinstall the blower assembly.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Air Handler codes

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 19. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.