Daikin Air Handler: ECM high voltage power circuit checks

Updated · by Aurora Star Tech Inc.

ECM high voltage power circuit checks on a Daikin air handler: Checks the line voltage feed to the ECM motor from the 5-circuit power connector.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECM blower in indoor air handler

Common causes of ecm high voltage power circuit checks

  • No supply voltage to indoor unit
  • Open wiring in the 5-circuit power harness

How to fix ecm high voltage power circuit checks: step by step

  1. Disconnect power to the indoor unit.
  2. Unplug the 5-circuit power connector to the ECM motor.
  3. Turn power on to the indoor unit.
  4. Measure voltage between pins 4 and 5. It should equal the indoor unit supply voltage.
  5. Measure voltage between pins 4 and 3, then between pins 5 and 3. Each should be about half the reading from step 4.
  6. If no voltage is present, check supply voltage to the indoor unit (see S-1).
  7. Disconnect power, then reconnect the 5-circuit harness.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Air Handler codes

Source: Daikin SiUS612209EA service instructions, p. 18. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.