Daikin Air Handler: ECM high voltage power circuit check
ECM high voltage power circuit check on a Daikin air handler: Checks the line voltage feed to the ECM motor power connector with the 5-circuit harness unplugged.
Applies to: ECM motor 5-circuit power connector
Common causes of ecm high voltage power circuit check
- No supply voltage to the indoor unit
- Open harness or connector
How to fix ecm high voltage power circuit check: step by step
- Disconnect power to the indoor unit.
- Unplug the 5-circuit power connector at the ECM motor.
- Turn on power to the indoor unit.
- Measure voltage between pins 4 and 5. It should equal the indoor unit supply voltage.
- Measure voltage between pins 4 and 3. It should be about half the step 4 voltage.
- Measure voltage between pins 5 and 3. It should be about half the step 4 voltage.
- If no voltage is present, check supply voltage to the indoor unit.
- Disconnect power, then reconnect the 5-circuit harness.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.