Service & test modes: Furnace tips (part 2 of 2)
Short, practical technician tips on service & test modes for furnace. Check each one against the manual for your exact model before acting.
Force high-stage gas heat for testing
Rheem · 96V and 96MDV series 2-stage communicating furnaces
Used to test high-stage gas heat with a communicating thermostat.
- Remove the communication connections from the thermostat (E1, E2).
- Jumper W1 to R and R to W2 to set high-stage gas heat.
- Set the FAN switch to AUTO on the thermostat.
- Set the thermostat to call for heat with a temperature differential above 10°F.
- Note the dip switch settings before testing and restore them afterward.
- Test mode times out after one hour; check that the thermostat does not switch to high fire or test mode is not timing out.
Force low or high fire for testing (RGPE/RGLE)
Rheem · Rheem/Ruud RGPE / RGLE modulating furnaces
Temporarily locks the gas firing rate and blower to low or high for the heat call already running, up to two hours or until the call ends. Will not engage without a heat call.
- Start a heat call at the thermostat
- Open SETUP in the furnace USER MENU and choose FIXED FIRE RATE
- Select low or high; the setting lasts for this heat call (max 2 hours)
Read or clear the six-fault history from the thermostat (RGPE/RGLE)
Rheem · Rheem/Ruud RGPE / RGLE modulating furnaces
The FAULT HISTORY user menu shows the six most recent faults, newest first, with the number of powered days ago. The last item, CLEAR FAULTS (yES / no), wipes the list.
- Open the furnace USER MENU at the communicating thermostat and select FAULT HISTORY
- Press the down arrow to step to older faults
- To erase, go to CLEAR FAULTS and pick yES
Carbon monoxide spillage test (vent check)
Trane · Draft hood appliances on a shared vent
Run before returning a furnace to service on a shared vent. Failure to follow this can cause carbon monoxide poisoning or death.
- Seal any unused openings in the venting system.
- Check the venting system for proper size, horizontal pitch, blockage, restriction, leakage and corrosion, per NFPA 54 / CSA B149.1.
- Close building doors and windows and the doors between the space and the other appliances.
- Close fireplace dampers.
- Turn on clothes dryers and any appliance not on the vent. Run exhaust fans such as range hoods and bathroom exhausts at maximum speed. Do not run a summer exhaust fan.
- Light the appliance under test and set the thermostat so it runs continuously.
- After 5 minutes of main burner operation, test for spillage at the draft hood relief opening with a match or candle.
- If spillage shows, correct the venting to code before continuing.
- Return doors, windows, fans, dampers and other appliances to their previous condition.
Read or clear the last 6 faults (L6F menu)
Trane · S8V2, S8B1, S8X1, S8X2
The L6F menu replays the six most recent faults and clears them from inside.
- Press Menu until L6F appears
- Press Option to enter and step through the faults
- To clear: inside the menu hold Option for at least 5 seconds, release; three dashes appear three times
Run test mode (furnace)
Trane · S8V2, S8B1, S8X1, S8X2
Lets the technician watch the inducer, igniter and blower step through stages without firing the burner or running the outdoor unit. Option holds a step (HLd). The test takes a short while to begin.
- Press Menu until run appears, then press Option; the display flashes three times and the test starts
- Steps: inducer 1st then 2nd stage (30 s each), igniter 10 s, then blower at 1st/2nd-stage compressor speed and 1st/2nd-stage gas heat speed (10 s each); the sequence repeats two more times
- Exit by pressing Menu briefly, cycling furnace power, or making a valid thermostat call
Read or clear stored fault codes with the LAST ERROR button
York · York IFC boards with LAST ERROR button
The board keeps up to five fault codes, newest first, through power loss. Solid-LED errors are not stored. Retrieval only works with no thermostat signal active.
- End any heating, cooling or continuous-fan call
- Press and release LAST ERROR (more than 1/5 s, under 5 s); the LED flashes the stored codes, most recent first, with a 2 second pause between
- TM9V: after the codes it returns to slow green flash after a 5 second pause; press again to repeat
- Two green flashes = nothing stored
- To clear, hold the button 5 seconds or more; three green flashes confirm
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.